ING Banner
Home > Astronomy > Wide Field Camera > Observing Guide > INT/WFC Operation Manual

INT/WFC Operation Manual

Contents

  1. Introduction
  2. Areas of the telescope
  3. Safety
  4. Preliminaries
  5. Moving the telescope out of access park
  6. Moving the telescope into access park
  7. Zeroset
  8. Initial TCS Commands
  9. Loading catalogues
  10. Readout speed
  11. Filling the cryostat
  12. Opening up
  13. Flat fields
  14. Single star calibrate
  15. Focusing the telescope
  16. Observing
  17. Special observations
  18. Closing down at the end of the night
  19. Closing down in a hurry
  20. Saving data
  21. Creating the observing log
  22. Filling the logbook
  23. Leaving the building
  24. Observers' handover check
  25. Acknowledgements

1. Introduction

In this guide, the following syntax will be used:
  1. The Systems prompts will appear in the text as type writer fonts, in the following format:
     USER> Commands to TCS (window on Telescope Control System)
      SYS> Commands to ICS after startobssys
    (Instrument Control System, pink window)
       ecl> IRAF commands
        $> Any other terminal window eg: xgterm
    Typewriter text indicates that that exact command should be used. For variable input, curly braces will be used, e.g {your_input}. So, where the example might say:
      SYS> sky {time}
    to take a sky flat of length {time} seconds, at the prompt you would type:
      SYS> sky 10
    to take a sky flat of length 10 seconds.
  2. Words in green correspond to actual buttons to be pressed.
  3. Words as hyperlinks go to corresponding pictures or further details.

2. Areas of the telescope

The control room is located at the top floor of the building, and has the following key areas:
  1. The Engineering Rack, with all manual movement controls.
  2. The Engineering Console, which contains the dome lights, engineering button lights, Emergency Stop and reset buttons, and the Computer/Engineering mode switch. There is also the TV showing the inside of the dome, and the speakers providing the sound.
  3. The ICS Screens, (Instrument Control System). A Mosaic of the various ICS windows can be seen here: ICS Windows
  4. The Meteorological Data Screen.
  5. The Whiteboard, containing lots of details and information.

3. Safety

  1. Before starting work at the telescope please make sure you read this important safety information!
  2. Please print and read this document very carefully. If you agree with all the items, please sign it and hand it to your support astronomer.
  3. Please use a lone worker alarm when you are observing alone at the INT. They can be found on the back wall of the control room (see here), on a black rack. They are specific to each telescope so should never be taken away. The orange buttons should only be pressed in a real emergency.
  4. For security reasons you must follow the instructions given to you by the support astronomer or WHT Telescope Operator (WHT OSA), eg. abandoning site in bad weather or regarding the operation of the telescope and instrument.
  5. For safety reasons there is a laser curtain installed in the elevator that will cause the elevator to stop if the light path is broken by a person or object. If this happens you may be stuck in the elevator. Also, due to its age, the elevator is not reliable. For these reasons we recommend that you don't use the elevator outside the Operations Team working hours (9:00 - 15:30), nor on weekends.

4. Preliminaries

  1. In the control room, first check the Operations Logbook for any restrictions that may be still in force. In the upper-left corner of the Operations Logbook, write the names of all observers who will be at the telescope during the night.
  2. Turn on the dome lights (MAIN ON/OFF) from the Engineering Console and raise the control room blind.
  3. Make a visual inspection of the observing floor (and the balcony above the control room if the telescope is at access park) to check that the telescope is free to move e.g. no ladders or steps are close to the telescope or test instruments connected.
  4. Clear any emergency overrides by pressing the RESET button next to the EMERGENCY STOP button on the console. If the light does not clear, check for emergency stop buttons that may have been pressed.
  5. Turn on the OIL PUMP from the engineering rack. The oil pump must be switched off at the end of the night, or when the telescope has not been moved for more than an hour (e.g. during bad weather).
  6. In any browser, open the new http://obslog.ing.iac.es ING Observing Log system, to see in near real time the acquired images and allow you to complete the night report at the end of the night. This section trains you how to complete the night report, then save the night log, at the end of the night.

5. Moving the telescope out of access park

  1. Turn the DEC QM variable speed control fully clockwise.
  2. Turn and hold the limit key-switch clockwise in the OR (override) position following the next few steps. The limit key-switch causes the slow motion clamps to re-engage.
  3. Push the DEC QM button to go back to Quick Motion. Note that both the SM and QM lights are lit when in Slow Motion. It is in Quick Motion when only the QM light is lit.
  4. Push the DEC[-] button. This will move the telescope up and away from the balcony.
  5. When declination is below 90 degrees you may release the limit key-switch. If the audible alarm sounds, push the ACCEPT button on the Engineering Console to mute it.
  6. To bring the telescope to zenith manually continue to push the DEC[-] button and stop at DEC=28d 45' (+/- 1 degree). This needs a bit of experimenting because the telescope will not stop immediately when you release the DEC[-] button. The telescope is now at zenith.
  7. Push the DEC SM button to re-engage the slow motion clamps. When Slow Motion is activated only the SM light is lit.
  8. Alternatively, once you are out of the override limit, switch to computer mode by turning the key on the Engineering Console. In order to do this four conditions must be met:
    • There must be no alarms pending (press the RESET button next to EMERGENCY STOP on the Engineering Console to clear).
    • The oil pumps must be switched on.
    • The telescope must be out of the override limit.
    • The declination and hour angle must be in Slow Motion (DEC[SM] and HA[SM]).

    Now, type:
     USER> park zenith 
    To park the telescope at zenith.

6. Moving the telescope into access park

  1. If the telescope has been zeroset since the last time the TCS was re-started then in Computing Mode type:
     USER> park zenith 
    There is no problem if an alarm starts to ring, just acknowledge ( USER> ack ). After the telescope stopped at Zenith, move it to the park position:
     USER> park ap1 
    If you're not sure then try typing the commands: if the telescope hasn't been zeroset it won't move.
  2. Switch to Engineering Mode by typing:
     USER> eng
  3. At the Engineering Rack, turn the DEC QM (Quick Motion) variable speed control fully clockwise, to quicken the process.
  4. In order to move to 106 degrees (access park), using your left hand, turn and hold the limit key-switch clockwise in the override position following the next few steps. The limit key-switch causes the slow motion clamps to re-engage.
  5. Push the DEC QM button to go to Quick Motion.
  6. Push and hold the DEC[+] button; the telescope will then stop at access park by itself. There is no danger in keeping the DEC[+] button pressed.
  7. Now you may release the limit key-switch.
  8. Bringing the telescope down may cause an alarm to activate as the mirror nears the vertical. Push the ACCEPT button on the Engineering Console to mute the alarm.
Had the telescope not been zeroset since the last time the TCS was re-started then the entire procedure would have to be done in Engineering Mode. You would first switch the telescope to Engineering Mode, as in point (2) above. Using Quick Motion you would move the telescope first to zenith. At zenith the telescope should be vertical, with the HA synchro indicator pointers at the "12 o'clock" position (HA = 0h), and the DEC indicator pointers around the "9:50" position (DEC = 29d). After this, using only the DEC controls, you would bring the telescope down towards Access Park, still in QM. The telescope should end up pointing in the direction of the control room window. Only when the telescope can no longer move any further down do you need to start using the override key switch, after which the procedure is as above, from point (4) onwards.

To avoid having to do this it is easiest to park the telescope at zenith before re-starting the TCS, should you be forced to do so.

7. Zeroset

The "Complete zeroset" of the telescope should be done only in the afternoon of the first night of your run by the SA. It could be also executed by the observer after any TCS restart or when the pointing is poor.

IMPORTANT: During all runs, the "Complete zeroset" must be run only by the INT SA student astronomer. This must not be run by the visitor observers during any another night. Visiting observers only need to run the "Abbreviated zeroset" in order to inherit the TCS pointing model from the previous night or the INT TCS default one.

IMPORTANT NEW REQUEST (26 Aug 2021):
Record an encoder log whenever the complete zeroset is done. The command sequence should be (in the TCS User window):
 USER> LOG ENC ON 10 
  ... Perform the complete zeroset ... 
 USER> LOG ENC OFF  

7.1 Complete zeroset

  1. Park the telescope at the zenith position (see section on moving the telescope out of access park), and switch to Engineering Mode using the command:
     USER> eng
  2. Check that the pointers on the Engineering Rack are on the correct sides for the zeroset, as indicated by the labels. If they are not you should move them to the correct sides using the HA[+]/[-] and DEC[+]/[-] buttons. The light above each dial will flash as the telescope moves through the zeropoint. This should be done in slow motion (SM).
  3. In the TCS User window, enter:
     USER> zeroset ha target         [or: zero ha tar]
     USER> zeroset dec target        [or: zero dec tar]
    n.b. These commands need to be typed in pair. If you type only one and then zeroset only that axis, it won't work.
  4. Using the HA[+]/[-] and DEC[+]/[-] buttons with slow motion (SM) selected and the SM variable speed control set to about half-way, move the telescope so that the synchro dial pointers move through the zeroset marks in both axes. This should be done in the same order they were typed, hour angle then declination.
  5. The TCS will beep if the zeroset is successful. The yellow LEDs mounted above the synchro dials will also briefly flash at the same time confirming that the telescope has been zeroset.
Note: Occasionally when moving through the zeroset position the yellow LED will flash but the TCS computer does not beep to acknowledge the zeroset, or vice-versa. If this happens, finish the entire zeroset procedure. Then move the telescope back to the pre- zeroset position, and redo the zeroset.
      USER> cal def                   Loads the default TCS pointing model.
Use on the first night of run.

7.2 Abbreviated zeroset

On subsequent nights of the observing run, and if the TCS has not been restarted, load the previous TCS pointing model:
      USER> cal last                  Loads the previous TCS pointing model. Should
be used on all subsequent nights of the run.

8. Initial TCS commands

These should all be typed now so that the telescope is ready for the night's observing. If the focal station is not the one you expect, contact your support astronomer.
      USER> show focal                Shows the focal station setup.
      USER> focus {x}                 Sets focus to a good value,
where x is the value shown
in the log book and on the whiteboard.

9. Loading catalogues

Start by checking which objects are loaded into the TCS current list of targets.
      USER> out term 
If there are objects loaded which you don't need, then the command
      USER> erase 
can be used to delete all targets from the current list. Note that the catalogues will still be stored on the computer, but will no longer be loaded into the TCS.

It is possible to load your own catalogue onto the TCS with all your targets in it. They can be created with any text editor, and should be saved as {your_catalogue}.cat, with no capital letters in the filename. Each line of the file should contain one object and its coordinates in the following format:
[object] [ra] [dec] [epoch] [!comments]
So, for an example object SN 1987A:
sn1987a 05 35 27.9 -69 16 10.00 J2000 ! comment  
The line must be delimited by spaces (one or more), but no tabs, and there should be no spaces or punctuation other than an underscore in the object name. They can then be loaded into the /int/cat/ directory on the ICS computer. This can be done using the scp command to copy the catalogue from your laptop to the data reduction computer (intdrpc1 or intdrpc2):
      your_laptop$> cd directory/containing/catalogue  
      your_laptop$> scp {your_catalogue}.cat intguest@intdrpc1:/home/intguest/  
and then, from the instrument control system:
      intobs@inticsdisplay$> cp /home/intguest/{your_catalogue}.cat /int/cat 
The catalogue can then be included using the command:
      USER> include {your_catalogue}   
Note that the .cat extension is not required.

It is also possible to add and remove individual objects using the following commands:
      USER> source sn1987a 05 35 27.9 -69 16 10.00 J2000  Creates object. 
      USER> add                                             Important! Loads
object into TCS.
      USER> remove {object_name}                            Removes object.  
      USER> out file {your_catalogue}                       Writes the contents
of the current TCS
catalogue to file.
Note that to add the object you must include the epoch. No error message will be shown if you do not, but the object will not load properly.

10. Readout Speed

Check that the readout speed being used is correct. This can be changed either from the SYS prompt using the commands:
       SYS> rspeed slow   
       SYS> rspeed fast   
or from the GUI by pressing the 'fast' or 'slow' button. The fast readout speed is ~10s faster than the slow. However, the fast readout adds read noise to your image, so if looking at faint objects for which it is the dominant source of noise then slow readout is recommended.

11. Filling the cryostat

Important! Wear safety helmet (with visor), apron and gloves when filling cryostats. Example.

Important! (since 5 Nov 2015) The cryostat on WFC should be filled at least every 16 hours. During normal working week days, the ops-team working at ING will fill it at midday, so observers should fill it just before and after the observing night. During weekends and public holidays, the observer at INT is in charge of ensuring that the cryostat is filled at intervals not exceeding the 16 hour limit. If for any reason the observer at INT cannot ensure that the cryostat will be filled within 16 hours, he/she should contact the WHT Operator to coordinate the filling of the cryostat with sufficient notice. Public holidays are marked in green in the ING schedule.

Please take extra care when working with dewars, particularily with the follwoing points:
  • There is a sticker on each Dewar telling users to use the other Dewar if the level reaches 30%;
  • There are two Dewars, and the one filled more than 30% should be used;
  • Ops-team fill the dewars before the weekend, so only create a fault report (FR) if both dewars are below 30% on a working day which is NOT the last working day of the week (typically Friday);
  • Users must not completely empty any Dewar;
  • The 30% full Dewar will be used in case the silicon filling tube brakes on the Dewar in use.
  • Please wait long enough (at least 5 minutes!) before removing the silicon tube (the silicon tube should NOT be frozen when it is removed, otherwise it will break).
These are the steps to fill the cryostat:
  1. The dewars are located at the balcony, and the telescope must be in access park for this procedure (see section on moving the telescope into access park).
  2. On the dewar top, check that the SILVER valve (gas vent) is closed. Vessels must be left pressurised.
  3. Use the indicator on top of the dewar, (by pressing and holding the black rubber button) to check the dewar contains enough LN2 (>25%). If it is lower, the smaller dewar can be used. Take care with the hoses as they are prone to breaking when cold.
  4. Check the pressure gauge: the pressure should be between 0.5 and 1.5 bar. Again, use the smaller dewar if this is not the case.
  5. Wheel the dewar carefully into position opposite the prime focus, with the earth wire, filler tube and pressure gauge at sensible positions.
  6. Connect the dewar to earth; use the earthing point on the hand rail to the right of the telescope.
  7. Fully insert the filler tube into the cryostat hole, going through the metal triangle, under the plastic tie.
  8. On the dewar top, check that the GREEN pressure build valve is closed. Then open the BLUE decant valve.
  9. Vapour will come out of the cryostat continuously while you are filling it. However, it is not full until liquid nitrogen is seen to be spilling out onto the floor. You will hear this as well.
  10. Close the BLUE valve.
  11. Wait a couple minutes for the filler tube to warm up (until it is not rigid anymore) and remove it from the cryostat.
  12. Move the dewar back to the position where you found it.
  13. Always note down in the Operations Logbook what time the cryostat was filled and the initials of your name.
  14. The cryostat must be refilled before the start of the night's observing, and again in the morning before you leave. In the event of leaving the telescope early (e.g. due to bad weather) fill the cryostat, then fill in a fault report so that the cryostat can be filled again in the morning by the operations team.

12. Opening up

  1. Check that the weather conditions allow for observations: the humidity is bellow 75%, the rain sensor is "dry" (no rain), and the weather was stable for at least 20 min.
  2. Set the humidity alarm to 75%. If it's already above that level set it to 90%.
  3. Check the binning, readout speed and windowing have been set correctly.
  4. Check that the IRAF window and Observing Log are both showing the correct directory for the date you are observing.
  5. Fill in the 'Who Goes There?' window with your proposal number and the name of the PI.
  6. Open the south doors, and the double doors between these and the dome for ventilation, if not too humid (>75%). If the wind speed is >40 km/h, or you close for bad weather the South Doors will need to be shut again. It is also the observer's responsibility to shut them at the end of the night.
  7. Turn off the lights in the area between the Control Room, the Dome and the South Doors and the Control Room Corridor.
  8. Ensure the lift (elevator) is at least one floor down and turn off its lights. Do not ride the elevator after 15:30 or during weekends!
  9. Take the stairs back up and turn off the lights at the far end of the control room nearest the South Doors.
  10. Using the CW (clockwise) and CCW (counter-clockwise) buttons on the lower engineering rack rotate the dome so that it points east, away from the sun. This should leave the dome over the doors on the left as you look through the window. Note that there is a compass laminated onto the desk in front of the Engineering Console.
  11. Turn off the dome lights on the Engineering Console.
  12. On the Engineering Rack, in the Upper Shutter panel, use RAISE MICRO to raise the shutter slowly, until you hear a 'clunk' and the Main Overtravel light turns off.
  13. Now use RAISE MAIN to raise the upper shutter, until another 'clunk' is heard, and the shutter stops moving.
  14. To fully open the upper shutter RAISE MICRO must be used again, until the 'clunk' is heard and the telescope stops moving.
  15. If observing at low elevation (<33 deg) then the lower shutter will need to be raised as well, in the same way as the upper shutter, using RAISE MICRO then RAISE MAIN. RAISE MICRO can then be used again to raise it the last small fraction. However, as the lower shutter is very large and blocks most of the upper region of the shutter space, this should not be done unless absolutely necessary.
  16. Push and hold the PRIMARY MIRROR OPEN button until all the petals are fully open. The telescope needs to be at or near access park in order to make sure they have opened fully.
  17. Turn the DOME VENT FAN on, on the Engineering Rack, to provide further ventilation. This should be turned off if the humidity rises above 75%.
  18. Move the telescope out of the override position (see section on moving the telescope out of access park).
  19. Close the control room blind.

13. Flat fields

    Twilight sky or dome flats should be acquired at least once per run to reduce WFC images. Preferably, they should have between 20000 and 30000 counts illumination, which could be measured in IRAF/DS9 with imexam (by pressing "c" for column cut over the DS9 window).

13.1 Twilight sky flats

  1. Include the blank fields catalog ("Table of 38 blank fields for sky flats" - newblank38 catalogue) using:
     USER> include newblank38   
  2. Move to an appropriate star field from the catalog using:
     USER>  gocat {field name}
    The field should have its RA within 1 hour of the current sidereal time, which is shown on the TCS Display window. If possible choose a wfc or wfs field, as these were especially chosen to be blank over large areas for the wide field camera. If one is not close enough, then one of the other fields will do.
  3. Select the appropriate filter using the GUI, remembering to first use narrow filters, then broadband filters, and typically moving from blue to red within each group in the evening. In the morning this will be the opposite way around.
  4. Use:
      SYS>   ftest 2
    to perform a two second windowed glance. Note that you must be in the /home/intobs directory to use this command. This will read out almost instantly, allowing the sky levels to be determined using IRAF on the data reduction machine using:
       ecl> display s1[1] 1; imexam
    By hovering the pointer over the background and pressing m the pixel values will be displayed, for the area covered by the pointer. The ideal level for the flats is between 20000 and 30000 counts, though anything from 10000 to 40000 counts should be useful.
  5. When the background drops to an appropriate level a flat field can be taken using the command:
      SYS>   sky {time}
    with the time expressed in seconds. Times shorter than 2s or longer than 120s are not recommended for flats. Remember that with the same filter, assuming the level was good for the flat just taken and you are using slow read out mode, the exposure time will need to be increased by a factor of 1.5 to account for the dropping background brightness in the evening. In the morning, of course, the exposure will need to be decreased by a factor of 1.5.

    The sky level can now be checked in IRAF using the command:
       ecl> display r{number}[4] 1; imexam
    again, using m to check the sky level. The {number} can be seen on the GUI. The fourth extension is viewed because this shows the middle chip.
  6. It is customary to offset the flats taken in the same filter, so that the images can be combined to remove stars later. This can be done using the command:
      SYS>   offset arc {arcsecRA} {arcsecDEC}
    with {arcsecRA} and {arcsecDEC} being the number of arcseconds you want to offset by. Note that {arcsecRA} and {arcsecDEC} are absolute values (based on the last gocat pointing) and not relative values (not based on the last offset). Therefore a different offset will be needed for each flat in the same filter to avoid having multiple flats in the same place.
  7. When changing filters the ftest script can again be used to check the sky levels so the correct exposure time is used for the flat. For the evening twilight flats, in general the flats should be taken in the broad-band filters from the blue to the red. For example, based on recent Apr 2022 WFC tests, the folowing order is recommended: U and V filters, then B and Sloan g, then Sloan r, and finally Sloan i.

13.2 Autoflat

    Autoflat is an automated flat fielding script written by the former ING TO and student James McCormac in 2014. Using the commands given below, the script takes a list of filters, prioritises them and acquires the number of flats requested. If the sky is too bright/dark for a given filter it will skip that filter and continue to check the next one. Once all flats have been taken or the sky level is out of range the script will end. A summary of the successful flat fields is printed at the end. Be aware, the script does not work yet with windowed or binned modes.
       SYS>   cd
       SYS>   cd jmcc/autoflat
       SYS>   /int/ObservingSystemSupportPackages/python-3.2.2/bin/python3.2 
            autoflat.py num_flats_per_filt rspeed f1 f2 ... fn
    where: num_flats_per_filt represent the number of flats in each filter, rspeed is the CCD readout speed (slow or fast), and f1, f2, ..., fn are the filter names for filters 1, 2, ...., n

    Example:
       SYS>   /int/ObservingSystemSupportPackages/python-3.2.2/bin/python3.2 
             autoflat.py 5 fast r stY stB Hbb 
    This will attempt to take 5 flat fields in fast readout speed in the filters Sloan r, Stromgren Y, Stromgren B and H-beta.

    The script does not work yet for the following filters: WFCWash51 (#223), WFCStrHbN (#225), all the NOVA filters. For these filters, flat fields shall be taken manually.

    The script can be aborted using Ctrl+C.

    After breaking the script, please check the binning, readout speed and windowing, as they are changed as part of the normal functioning of the script.

    The autoflat script aims to fulfil the following criteria: MAX counts: 40,000; MIN counts: 20,000; TARGET counts: 30,000; MAX exptime: 120s; MIN exptime: 1s.

    The filters are prioritised first by bandwidth into broad (B) and narrow (N), then each group of B and N are prioritsed according to central wavelength. Use typically blue-to-red in the afternoon and red-to-blue in the morning.

13.3 Dome Flats

    Dome flats could be acquired if twilight flats could not be taken for some filters. For this, the dome shutter should be closed and mirror petals opened.
     USER> park flat    Sends the telescope to the right position for dome flats
    The telescope should now point to hour angle 0 0 0, declination +80 0 0. Now move the dome to position 242 by typing the command:
     USER> dome 242     Sends the dome to the right position for uniform illumination
    The main dome lights should be closed, and the dim lights should be opened from the horizontal button located in the right part of the door going to the dome, and the knob should be turned somewhere at 2/3 or full position. In the WFC Dome Flat Assistant we give a table for some guides about exposure times to be used with the WFC and different filters.

14. Single star calibrate

On the first night, the default pointing model should have been loaded in the initial TCS commands, and is likely to be accurate. However, it is good to check it and make an additional correction with the following procedure. First, check the lower shutter which should be in the low (default) position.

       SYS> agwin acq pos 1032 512    Sets readout to the centre
of the autoguider chip.
       SYS> autotv on                 Turns on continuous readout mode. 
On the autoguider window mark a cross in its centre by selecting TOGGLE CENTRE CROSS from the SETUP menu.
      USER> cal faint                 Sends the telescope to a
suitable calibrate star.
When the HANDSET menu appears use <ctrl-z> to break out of it.
      USER> aper 5                    Changes the telescope pointing
to the autoguider centre.
If the star appears right on the cross-hairs then the pointing is okay, and the rest of this section can be skipped. Otherwise, press the HANDSET button (INSERT) to centre the star on the cross-hairs in the centre of the autoguider window.

In case no star is visible in the autoguider window, check on the GUI if the camera shutter is open, according to these instructions.

Points to consider:
  1. Bear in mind that arrows move the telescope and not the sky. So think of it as moving the cross to the star, and not the star to the cross.
  2. Pressing a direction button once moves the star by the increment size value shown in the TCS window, near the top. The increment can be changed by using the '<' and '>' buttons.
  3. After pressing a key, wait until the autoguider window has refreshed showing the new position.
  4. In case the star is either too faint or saturated, then the exposure time can be changed by going to SELECT -> INTEGRATION TIME -> SELECT FROM MENU.
Once the star is well centred, press handset and type:
      USER> point calibrate           Writes the new pointing model to file.  
      USER> cal anal zero             Loads the new pointing model 
The rms of this solution is typically 0.01, because only one star is being used. Type 'Y ' to accept.

Prepare the telescope pointing back to the centre of chip 4:
 USER> enter aperture 0 -251 326
       SYS> autotv off                Turns off continuous readout mode. 
Note: If the pointing is still bad after the single star calibrate, then refer to the troubleshooting guide. First try zerosetting the telescope again, the default calibrate and then the 7 star calibrate if necessary.

15. Focusing the Telescope

The typical "default" WFC focus is around 43.35 and the last night value is written on the white board. If the seeing is unstable (changing rapidly) or bad (> ∼2 arcsec) do not attempt to focus the telescope. Instead, you can adopt the focus from the last night. If you need to determine focus values in more filters, use preferably broad band filters first, which need lower exposure times, and afterwards narrow band filters, if sky conditions are stable. Otherwise you could rely on filter offsets if they are known in the filter database. Focusing in narrow band filters needs longer exposure times (at least 2-3 times or more) than in broad band filters.

To determine the best telescope focus select a suitable field (e.g. one of the WFC photometric standard fields). Choose either a field close to your first target, or continue using the same field as the single star calibrate. Sometimes these fields can be too crowded and in that case try a suitable blank field.
   SYS> gocat {suitable standard field}  
Then make sure the camera is not windowed (disable any eventual defined window),
   SYS> window 4 disable
and run the focus script.
       SYS> focusrun &  
Note: Complete the focus run in a suitable filter. The reddest filter in the wheel is desirable, since it will have the smallest FWHM for a point source.

Note: After the fucusrun, it is important to check that the detector configuration was correctly restored and it is recommended to take a glance to confirm.

A dialog box will pop up and the appropriate values may be filled in and a focus run started. The default values should be good, but the recommended values are:
Number of exposures (n)      =        9 
Focus start value            =        0.2mm below last known focus (see white board)
Step size                    =        0.05 mm 
Exposure separation          =        10 arcsec 
Exposure time                =        15 sec 
  1. Hit RUN. All n exposures will be taken on the same frame, giving lines of repeated stars. There is a double space between the first and second exposures to make them easily identified.
  2. Accept any error box messages and close the focus run window.
  3. Next, type:
       ecl> wfc_starfocus
    to compute the best focus value from the focus run. It will ask you which run number the focus run is, and the number can be found on the GUI. It will know all the values you selected for the run. If the command is not recognised then you may need to load the package for it by typing:
       ecl> wfc_ql
  4. It will ask you to identify as many first stars as you want, 10-12 being typical. This is done by placing the cursor over the first star of a set and hitting 'm'. Make sure that the whole line of stars is on the CCD, and that the stars you pick are clear single stars and not obscured or saturated. Pressing 'q' when finished produces a graph showing what it believes to be the best focus value. Quit display window with 'q' before closing it.
Remember to set the best focus value at the end of the focus run using the command:
      USER> focus {value}
If the target is needed back at the original position then the gocat command will need to be repeated.

Enter the value obtained on the whiteboard and in the log book.

If, after running the focus script, the stars are still very unfocussed or doughnut-like instead of point-like, then the focus run can be done again using a larger step size and more steps as appropriate. A 0.1mm step size with 11 steps may be a good next try.

Note (related to FR 22542): Be aware to the TELFOCUS in the WFC FITS image headers, which seems variable in time after a given setup. This information in the headers is actually false, the actual telescope focus being constant, with the old UNIX TCS software being responsible for this minor apparent change in the headers. There is no failure in the focus mechanisms and both the telescope and the instrument are working just fine.

16. Observing

This section acts as a glossary of standard commands, but is organised into progressions of tasks and order of use. Note: it is strongly recommended to use guiding for exposures of longer than two minutes.

16.1 Lower shutter

You must close the mirror petals anytime you move any dome shutter!

Remember that the lower shutter starts to vignette at an elevation of 33 deg. The system does not warn you. If you need to observe at elevation <33 deg then the lower dome shutter must be raised (see section on opening up). Then you can observe targets with altitudes between 20 deg and 34 deg without any shutter obscuration.

Remember to open the petals, once you prepared the shutters for observing.

16.2 Acquisition

Loading catalogues and objects is described in the section Loading Catalogues. To move to one of these objects:
       SYS> gocat {object}            Telescope will slew to that object,
which must be loaded into the TCS,
and track it, e.g.
       SYS> gocat 92-248              Moves the telescope to the Landolt field
92-248 which is stored in the system catalog.

16.3 Filters

       SYS> filter {filter}           Changes filter. Use the same format
as seen in the GUI wheel, e.g. Ha, r.
Alternatively, just click on the filter
wanted in the GUI.
A de-focus term will automatically be applied when you change filter. It can take a few seconds to finish changing focus, and this can be seen on the TCS information screen.

16.4 Guiding

Check that the autoguider tv-mode is off. If it is on, type:
       SYS> autotv off
When the gocat command has been executed to slew to a new field then a list of guide stars will appear in the Talker window. This list can also be seen by entering:
       SYS> more /tmp/gsc.out
If this does not occur then check that the auto predict is on (see section on finding guide stars in the troubleshooter).

The guide window size can be set in the GUI under the settings tab. A size of 120x120 pixels (resulting in a sky field 45"x45") is recommended.

A guide star of appropriate magnitude should be selected from this list. To guide on this star use the command:
       SYS> guide on pixel {x} {y}
with {x} and {y} being the same values as before. If the guide star doesn't appear within the window you can try a larger window size (for instance 180x180 pixels under "Settings" on the GUI) or do the following:
       SYS> guide off
       SYS> agwin acq pos {x} {y}
       SYS> field
This centres the AG on the position where the guide star should be and searches for potential guide stars within that field displayed. They will be marked and numbered on the autoguider. Sometimes this command needs to be issued twice before it works.

To guide on one of these stars, use the command
       SYS> guide on star {n}
where {n} will be a number assigned to each star, being 1 the brightest. Be aware that the field command often picks up artifacts, so you should always check that you are guiding on a real object. For this reason it is recommended not to use scripts for setting up guiding.

Before starting the exposure it's important to leave the autoguider to settle. When guiding, the TCS will display A/G on rather than tracking, and show the x and y errors in the guiding. These should be allowed to drop below 0.3, though if the seeing is bad the errors may not get lower than 0.5. It can take a few readout cycles for the errors to be displayed in the TCS. If you do not see them then the guiding is not working.

NOTE: After setting a new exposure time for the autoguider, you should close the popup window with the buttons provided and NOT the X button (at top right of the window), since doing the latter prevents display of the popup again.

NOTE: When using long autoguider integration times, then increase the wfc_ag_sequencer time before readout to be integration time + 9s.

It usually takes some time to turn the guiding off (SYS> guide off). If it takes too long, then use <ctrl-c> to exit it, then check guide job ID number and kill this process:
       SYS> autotv off
       SYS> jobs
       SYS> kill 'job_number'
The command to turn the guiding back on is:
       SYS> guide on

16.4.1 Autoguider sequencer

The aim of the so-called "guiding sequencer" (the wfc_ag_sequencer program) is to avoid extra noise (interference) on science images if they are read out while autoguider is reading out. The following two cases are possible:

Observing programs using guiding (exposure times longer than 2-3 min), the sequencer must be always used, so the sequencer should remain active (red flag checked) during the whole run. Also note that any TCS restart will start/default the observing system with the sequencer active.

Observing programs not needing guiding (but only tracking) for their short science exposures (less than 2-3 min) should un-mark the sequencer by pressing in the small window on red click button (un-press it) to dis-activate. Also, observers should un-mark this option after each TCS restart.

When observing guiding for time-series measurements, it is best to change the command in the sequencer to "guide on pixel {x} {y}" where {x} and {y} are the coordinates given when starting the guider. This will help minimise drifts between exposures.

16.5 Not guiding

For short exposures (under 2-3 min) you may want to turn off the autoguiding. This can be done using the command:
       SYS> guide off
Remember also to turn off the sequencer by turning off the enable button on its GUI.

NOTE: By default in guiding mode, the sequencer stops autoguiding 10s before the WFC science image readout, in order to avoid this noise, but you can change this value (thought, it should not be less than 8s). If you do not need guiding for your science, then you should stop the autoguiding and sequencer using the above two actions, or using the following sequence commands:
       SYS> guide off 
       SYS> jobs 
then look for which job is connected with wfc_ag_sequencer, and type:
       SYS> kill %n 
where n is the corresponding job number. If you decide to guide later because you are doing longer exposures, if the sequencer GUI is not on screen then it can be started using the command:
       SYS> wfc_ag_sequencer & 

16.6 Dithering

Dithering can be done in several ways, and which is most useful will depend on if you're using guiding and the size of the offsets you wish to use.

Offsets can always be applied using the command:
       SYS> offset arc {arcsecRA} {arcsecDEC}
Note that the {arcsecRA} and {arcsecDEC} offset shifts are in the RA and DEC directions, expressed in arc seconds. The offsets are relative to the last pointing, with the original position at {0,0}. Therefore, if you keep issuing the same offset, then the telescope will not move.

If you're not using guiding this will be the easiest way to perform all your offsets. If you are, however, then complications can arise, because guiding must always be turned off before using the offset command, otherwise the guiding will move the telescope back to its original position.

If you're guiding and making offsets small enough to keep the star within the field of the autoguider, then the field command may be used to locate it once again:
       SYS> guide off
       SYS> offset arc {arcsecRA} {arcsecDEC}
       SYS> field
       SYS> guide on star {n}
Where {n} is the number assigned to your guide star.

If your dither positions extend over a range >1 arcmin then you will probably find the guide star moving out of the field. In this case the easiest thing to do is calculate multiple dither positions for the object you're looking at beforehand, and then load them from a catalogue. Doing this allows you to gocat to each new position, and when the gocat command is used new positions for the guide star will automatically be calculated. There is a tool on the NASA Extra-Galactic Database (NED) to help you convert offsets into RA and Dec.

You would then use the commands:
       SYS> guide off
      USER> gocat {new_dither_position}
       SYS> more /tmp/gsc.out                  Find suitable guide star.
       SYS> guide on pixel {x} {y}
Remember to let the guiding settle before starting your exposure, so that the errors shown on the TCS display are <0.3.

Please note that if you want to mosaic images using all four chips then, because of the chip gaps, you will need to offset by at least 30 arcseconds in both x and y. This is due to the layout of the chip, which can be seen here: offsetting in just x or y merely causes you to move along the gaps.

Should you have any questions about dithering please direct them to your Support Astronomer, preferably in advance of your run.

16.7 Exposing

Before taking any sky exposure, make sure the dome has finished rotation to the new target, checking in the TCS Display window that the DOME label is not flashing!
       SYS> glance {time}                      Take a glance of {time} seconds. 
Stored as s1.fits (which will be overwritten). Use it to check you're on the right field or to estimate exposure times before the actual run.
       SYS> bias                               Take a bias frame.
       SYS> flat {time}                        Take a dome flat of {time} seconds.
       SYS> sky {time}                         Take a sky flat of {time} seconds.
       SYS> run {time} {"comments"}            Take an exposure of {time} seconds
with the {"comments"} added to the
header of the fits file.
For multiple biases, flats, skyflats, runs or glances, simply prefix the command with 'mult' and put the number desired directly after the command, e.g.
       SYS> multrun {n} {time} {"comments"}    Take {n} exposures of {time}
seconds, adding the {"comments"}
to the files' headers.

16.8 Windowing

For time resolved photometry windowing data can be a useful way to reduce readout time. Note that only chip 4 of the WFC can be windowed. This link shows how the readout time varies with window size (and binning). The window size can be set with the command:
       SYS> window {n} "[{x1}:{x2},{y1}:{y2}]"
To enable this window type:
       SYS> window {n} enable
and to disable type:
       SYS> window {n} disable
The window size and whether it's enabled can be seen on the GUI.

NOTE: Please do not attempt to use the entire CCD4 as a window (with or without any binning option)! This will crash the system, plus there will be no gain in readout time (which is the same as using the entire 4 chip camera).

16.9 Apertures

With a gocat command the telescope is sent to the RA and DEC specified for the object, so that this object appears in the middle of the centre chip (chip 4). Occasionally, it may be desirable to centre the object in a different position, and for this apertures can be used.

Aperture 0 is an absolute measurement and sets the centre, from which point all other apertures will be measured. This is the default pointing for the telescope and is set at -251" 326" (expressed in arcseconds), the centre of chip 4. All other apertures have values relative to aperture 0. Apertures 1-5 point to the middle of chips 1-5 (where 5 is the autoguider). This means that aperture 4 is defined as 0 0.

To see a list showing the different apertures set, use the command:
      USER> show apertures
If, for example, you wanted to have the object you're pointing at to appear in the centre of chip 1, then simply gocat to that object and then type:
      USER> aperture 1
This pointing will only be used for one command before reverting to its default pointing, so the aperture command should only be issued just before you want to use it.

If it's necessary to reset the pointing of the telescope for more than one target, and you don't want to keep re-typing the aperture command, then it is possible to redefine aperture 0 so that it has this new value as the default pointing. Extreme care should be taken when doing this, however, to return the telescope to its normal pointing afterwards. Also note that when this is done apertures 1-5 will no longer point to the centre of chips 1-5, since those values are set relative to aperture 0.

The command for doing this is:
      USER> enter aperture 0 {x"} {y"}
In general, this should only be necessary if a seven star calibration has to be performed, and this procedure is explained in detail in the Troubleshooting Guide.

16.10 Observing scripts

We list here two kind of scripts for WFC automate observing:

16.10.1 ING dithering scripts

Effective 25 Jun 2018, we are offering two new WFC dithering scripts (written in Python v. 3.2) named WFCdithtrack.py and WFCdithguide.py for 2-point (AB nearby fields), 4-point (ABCD neighbour field) or 9-point (ABCDEFGHI neighbour fields) in tracking (first script) or guiding mode (second script).

The guiding script WFCdithguide.py is capable for both small dither offsets (max half guiding window, by default 10") and larger offsets (larger than half guiding window, but having longer overhead time). You can lauch these scripts by pointing the telescope to the target, then type:
       SYS> WFCdithtrack.py
or
       SYS> WFCdithguide.py
then answer the few options.

Two similar older 2017 scripts (written in TCS language) offer small dithering and change of filter in tracking and guiding mode. They could be run as:
      SYS> dither_script_tracking
or
      SYS> dither_script_guiding
One can also copy them with another name (ex. dither_script_tracking_john) and change them to suit your needs, but these changes are observer time-risk basis.

16.10.2 Other user defined scripts

The observers could use their own observing scripts to observe a given sequence, given an object (ex. obj1) previously defined in the catalog, using standard observing commands (example of guiding with small dithering here: wfcsamplescript).

First, from your laptop you have to FTP your script (example johnscript) to the INT system:
      sftp intobs@intdrpc1
Second, you have to change directory to:
      sftp> cd /home/intobs
Third, you have to put your script there:
      sftp> put johnscript
Fourth, change its permission for execution there:
      sftp> chmod 555 johnscript
Finally, from the INT ICS terminal in the same /home/intobs/ directory, you can run the script by simply entering its name at the prompt, namely:
      SYS> johnscript


Here are two lists including commonly used WFC scipts written by ING staff or past observers (internal links):

Astronomy Ad Hoc Software
List of commonly used INT scripts

16.11 Examining data

If IRAF is not open on the data reduction PC then type iraf into a terminal window. This will open up an xgterm window, a DS9 window and execute IRAF automatically.

The data being collected will be stored in the directory shown on the GUI, which is /obsdata/inta/yyyymmdd with the last directory being the date on which the night starts.

Data can be looked at in the /obsdata directory but not reduced, and must also never be moved or deleted. If you plan to reduce the data on that machine then it should be copied to the /scratch directory, in which you may make your own sub-directory.

Data can be displayed in the ds9 window using the command:
        ecl> display r{number}[4] 1
This loads the contents of extension 4, corresponding to CCD4, of image r{number}.fits to the ds9 display. The {number} for the exposure is found on the GUI, or in the night log. If the exposure was windowed then the image will be written into extension 1. If a glance was taken instead of a run, bias, or flat then the image will have been written to file s1.fits.

The image can then be examined using the imexam task:
        ecl> imexam
Useful imexam commands include:

'v' for vector cut; click start and end
'c' for column cut
'l' for line
'e' for elliptical plot
's' for surface plot
'a' for text statistics
'm' to obtain pixel statistics on section around cursor
'r' for radial profile
'q' to quit imexam

imexam commands are listed on the desk.

Alternatively, the display and imexam tasks can be combined in one line by using a semi-colon:
        ecl> display r{number}[4] 1; imexam
Important: To match correct sky orientation (North up, East left, needed to correctly match star charts), in DS9 one should rotate CCD1, CCD3 or CCD4 images by 270 deg (Zoom/270), while CCD2 should be rotated by 180 deg (Zoom/180).

If you want to display all 4 different buffers (corresponding to the four CCDs) at once, then this can be done using the command:
        ecl> wfc_display r{number}
The 'tile' option must be selected under frame.

We recommend the following star chart server to identify the field: DSS STScI. On the form, you must introduce the RA and Dec corresponding to the INT pointing (typicaly centre of CCD4), set Height=11, Width=22 (corresponding to CCD4 field), change File format to GIF, then press Retrive image. The resulting star chart should match exactly the WFC CCD4 (as displayed and Rotated 270 deg in DS9).

16.12 New "talkerBellINT" command

Since October 2015, one could use the following new command to ring a bell sound after finishing any exposure, example:
        SYS> run 20; talkerBellINT

17. Special observations

17.1 Observations below 33 degrees

If you wish to observe at a zenith distance between 57 deg and 70 deg (33 deg - 20 deg elevation), then you need to raise the lower shutter (see section 12 of the INT/WFC Operation Manual).

There will not be any warning given from the TCS if you are observing the inside of the dome, so you will have to check the zenith distance (ZD) on the TCS monitor from time to time. Alternatively please check this INT visibility plot.

Please consider if opening the lower shutter is essential. Opening up takes around 10 minutes and the image quality will decrease due to observing through higher air masses.

Remember to bring the lower shutter down afterwards, as you will not be able to observe above 34 degrees elevation if it is left in the raised position.

17.2 Observations of moving targets

Moving targets (such as asteroids, comets or planetary satellites) could be observed with the INT in both tracking or guiding modes using non-sidereal (differential) telescope moving rates.

If you wish to observe such a moving target, then you need to compute its motion rates in the equatorial coordinate system. The TCS requires the differential tracking rates to be expressed as:
    da = d(alpha)/dt in SECONDS/sec
    dd = d(delta)/dt in ARCSECONDS/sec
Sometimes, ephemerides are given as
    d(alpha)/dt x cos(delta) in ARCSECONDS/hour (1)
    d(delta)/dt in ARCSECONDS/hour (2)
Thus, to transform these for TCS input, compute
    da = (1) / (3600 x 15 x cos(delta))
    dd = (2) / 3600
In case the ephemeris server gives you two options, chose "coordinate motions" instead of "sky motions", so you don't have to divide da by cos(delta) anymore.

The differential tracking rates are then input to the TCS using the following sequence of commands:
 USER> gocat {object name}
 USER> diff_rates da dd
 USER> next
To return to sidereal tracking (e.g. for standards) issue the TCS command:
 USER> diff_rates 0 0
The science exposure time when using guiding at differential rate is limited by the object's proper motion and maximum WFC available autoguider window size (recommended bellow 120x120 pixels, namely 40" box size).

18. Closing down at the end of the night

  1. If running, stop the autoguider:
      SYS> guide off
    The sequencer should also be turned off by depressing the enable button on its GUI.
  2. Bring the telescope close to access park by typing:
     USER> park zenith
    followed by:
     USER> park ap1
  3. Push and hold the PRIMARY MIRROR CLOSE button. Check the mirror petals close fully (petals can be seen moving through a gap in the telescope structure).
  4. Push the DOME VENT FAN STOP button to turn off dome fans. The red light will go on when the fans are stopped.
  5. In case of ice or snow conditions, move the dome shutter to the South (USER> dome 212 ) so the ice could be melt by the sun.
  6. Once the telescope is stopped, switch the TCS to engineering mode by typing:
     USER> eng
    The ENG/COMP push button should now be illuminated with a yellow light.
  7. If lower shutter has been raised close the shutter using LOWER MICRO, then LOWER MAIN, then LOWER MICRO until you hear a 'clunk' at each step.
  8. Close the upper dome shutter pushing LOWER MICRO until you hear the 'clunk', then LOWER MAIN until the shutter stops moving, and makes a 'clunk'. To finish closing, press LOWER MICRO until the shutter stops moving.
  9. Bring the telescope fully down into access park. (See section Moving the Telescope into Access Park).
  10. Turn off the OIL PUMP from the engineering rack. The light will show green.
  11. Close the South Doors if they have been opened.
  12. Fill the WFC cryostat following the same procedures as at the start of the night. Leave the telescope at access park.

19. Closing down in a hurry

If it starts to rain or snow, the humidity rises above 90% or the winds above 80km/h you will be forced to shut down in a hurry. If this is the case:
  1. Stop the current exposure and read out. To do this break out of the command and return the SYS prompt using <ctrl-z>. Then type:
      SYS> finish
  2. Close the mirror petals.
  3. Park the telescope using the command:
     USER> park ap1
  4. While the telescope is moving hit the DOME SHUTRS button next to the Engineering Console, so the dome shutters may be moved at the same time as the telescope.
  5. Close the mirror and the dome in that order (as in the section Closing down at the End of the Night), remembering to close the lower shutter before the upper if it is open.
  6. Shut off the fans.
  7. Close the South Doors.
  8. If you were using a 'mult' command then typing finish will not have stopped the remaining exposures from being taken, and the run must be aborted. This can be done by hitting 'abort' on the GUI, and then by typing:
      SYS> abort
  9. Release the DOME SHUTRS button on the Engineering Console for the dome shutters. If you forget to do this the dome will not track with the telescope.
  10. Visually check that the telescope has returned to ap1 correctly without twisting. If it hasn't issue the commands:
     USER> park zenith
    followed by:
     USER> park ap1
  11. If shut down for a long period of time then turn off the oil pumps. Do not forget to turn them back on before you move the telescope again.
  12. If abandoning the telescope due to bad weather then fill the cryostat before leaving, and fill out a fault report with the time you filled it so that the Operations Team can refill it first thing in the morning. Note that only time lost due for technical reasons should be included in the fault report. If abandoning due to high humidity turn the alarm off (middle setting) to stop it going off all night.

20. Saving data

With WFC, you can save your data either on DVD, on a DAT tape, or directly to your laptop or hard-drive. You only need to write your copy disk/tape, there is no need to write an archive tape.

20.1 Recording data on DVDs

DVDs can be burnt on either of the two Linux public computers in the control room (INTDRPC1 and INTDRPC2). Please refer for details to the following document (also shown on the wall to the right of INTDRPC1): http://www.ing.iac.es/Astronomy/computing/recording.html.

20.2 Direct to laptop

Data can be transferred directly to your laptop through the INGEXT network. Please refer for details to the following document http://www.ing.iac.es/Astronomy/computing/recording.html.

21. Creating the observing log

Fill in the night report (even if the weather was bad and you could not observe!) by selecting 'night report' which is situated in the observing logger window on the ICS monitor. Fill out all fields, and when done hit 'create log'. A copy called run_log_yyyymmdd.int is put in the observation directory so you can copy it when copying your data, and there is an option to email it to a comma-separated list of addresses. Please note that from March 2011 the online logs no longer show information on the targets observed for a proprietary period of one year. They only show the names of the observers, causes and amount of time lost and weather information for the night. If you arrive home and find you have lost your copy of the log please contact your support astronomer to obtain another.

Since June 2022, the new ING Observing Log web-based night logging system must be used to enter and show any night reports. To use it, must load in any web browser http://obslog.ing.iac.es, which should load by default the current INT night form - otherwise, please type for example http://obslog.ing.iac.es/20221110/INT, eventually changing the date 20221110 accordingly. This form should load in near real time all images (including the ones most recently taken). At the end of the night, if you scroll down the page to the end, you will see a button End-Of-Night Report (leave active or eventually change to INT under the other button Chose telescope), which must be pressed to get displayed the Night Report form, able for completion. Please complete all fields there, then scroll down the page at the bottom, then press the two buttons Save to database and Save to /home/lplogs!

22. Filling in the log book

The printed logbook in the control room contains fields which must be filled out during the night:
  1. CCD cryostats : initials and local time for filling the cryostat.
  2. Breakdown of observing time: fill in any down-time that was encountered (bad weather, technical problems, etc.) and note the time lost.
  3. The last focus used during the night. This can be found next to focus on the TCS display.

23. Leaving the building

Before leaving the building, please switch off all major lights in the control room and in the kitchen area. Check that no electrical devices are left on in the kitchen, e.g. sandwich toaster, coffee machine, etc.

24. Observers' handover check

Ready to go it alone? Please check you are familiar with the following tasks:
  1. Use of telephone: numbers on right edge of whiteboard.
  2. Safety precautions when using liquid nitrogen.
  3. Weather precautions, knowing when the dome must be closed (also on whiteboard).
  4. Observing at zenith distance between 57 and 70 degrees (see troubleshooter).
  5. Opening and closing the dome.
  6. Moving the telescope in engineering mode.
  7. Starting up and shutting down the observing system.
  8. Knowing about the most common faults and how to solve them.
  9. Writing your data to an external hard drive or dvd at the end of every night.
  10. Filling in fault reports.
  11. Filling in the log book in control room.
  12. Producing the observing log.
  13. Filling in the observing feedback form at the end of your run.
If, after reading through this guide and the Troubleshooter, you are still having problems you cannot solve then you can ring the WHT OSA. Numbers are found on the whiteboard.

25. Acknowledgements

Credits should be given to the following ING students who contributed to improve this manual: Hugo Ledo, Dora Fohring, Lee Patrick, Liam Hardy, Mansour Karami, Yudish Ramanjooloo, Inaki Ordonez, Fatima Lopez, Manuel Diaz Alfaro, Luis Peralta and Abel de Burgos.


Top | Back


WFC Instrument Specialist
Last modified: 11 Nov 2022 (ING new Observing Log system)