Electrical enhancements following Bureau Veritas inspection

  Original Bureau Veritas report (Spanish)  English version

ING assessment safety critical issues and recommendations

Independent assessment of safety critical issues and recommendations by Onazol

     
         
 
no. Identification component Problem Responsible Cost Status
1 Distribution board connection checks Loose connections cause fire hazard   780 50% INT completed
2 Replace emergency lighting units with dual feed Dual feed could cause electrical danger contractor 1,540 contractor identified needs planning
3 Voltage returns within distribution boards Could be caused by item no.4 contractor 540 Completed
4 Cable colour coding Does not comply with current standard contractor 3,120 Generator house + INT completed
5 Emergency lighting at fire extinguishers   contractor 8,447  
6 Mains supply earth and neutral bonding earth & neutral connect together in distribution room ING low Completed
7 Replace circuit breakers (including replacing distribution boards) Rated to low contractor 14,640  
8          
9          
10          